Cabinet surge protection DC – Cable glands

    Product Details

    Product Description

    For photovoltaic installations up to 800VDC
    With surge protection DC type 2 and switch-disconnector DC
    Consistent with UTE C15-712-1
    Fitted and pre-wired in Cabinet IP65
    Warranty: 2 years
    Presentation
    According to standard UTE C15-712-1, surge protection is mandatory DC side in the presence of lightning or for certain facilities depending on the length between panels and inverter and lightning strike density (the density of lightning strikes is established by Department).
    In addition, revision 1 of standard UTE C15-712-1 requires that the disconnecting device is not integrated into the DC/AC converter.

    Lightning protection DC for photovoltaic systems assembled by AIGER Cabinet allows to respond to the two points of the standard and is intended for the protection of the photovoltaic installations upstream of the DC/AC converter.
    All our surge protection cabinets comply with standard IEC 60364-7-712 'Facilities in the building - part 7-712 - rules for special locations - photovoltaic power supplies and facilities'.


    Characteristics of the SPD

    SPD type 2
    Plug-in cartridge
    Maximum continuous operating voltage: 1000 VDC
    Nominal discharge current: 20 kA
    Maximum discharge current: 40 kA
    Level of protection under the nominal current: 3.6 kV
    Response time: < 25 ns
    Connection capacity: 4-35 mm2
    Operating temperature:-20 ° C to + 80 ° C
    Integrated thermal disconnection
    Complies with IEC 61643-1


    Characteristics of the switch-disconnector

    Switch-disconnector 4-pole mounted in series 2 by 2
    Maximum current:
    32A under 500 VDC
    20A under 600 VDC
    15A under 800 VDC
    Lockable in position 0
    Complies with IEC / EN 60947-1 and IEC / EN 60947-309

    Characteristics of the Cabinet

    Box in ABS grey RAL 7035 modular 8-slot IP65
    Dimensions:

    Customers Who Bought This Item Also Bought